Recovered ID Enquire

Standards

The standards printed on a shrink tube datasheet, decoded

>20 kV/mm, 12 kV/mm, 14.3 kV/mm — one property, one manufacturer, two test methods behind it. Read the method column before the value.

Twelve references sit on the GSC thin wall sheet: seven ASTM methods, IEC 216, UL 224, two MIL specs and CSA C22.2. One row on it, heat shock at 250 °C for four hours, carries no method at all.

They are not one list. Sort them by what each governs and four groups fall out. Two were run on the compound you are buying. One is checkable without asking the manufacturer for anything. One is about the factory.

Four groups, and the one a specification should name

Type specifications fix what the tube must be. MIL-I-23053/5 and IEC 60684-3-247 are the two here. One document carries the dimensions, the tolerances and the property set, which is why a utility or defence clause names one of these and not a test method.

A listing is the flame evidence. UL 224 with a VW-1 rating is the only reference in this range tied to an outside body's file number, and a file number can be looked up.

Bench methods are everything else: nine ASTM methods across the heat shrink range, plus IEC 216, ESI 09-11 and MIL-I-7444. Each returns one figure from one specimen under one stated condition. None of them rates a joint.

Company certificates describe the factory, not the tube. ISO 9001:2015, ISO 14001:2015 and ISO 45001:2018 cover how it is run. CPRI certified 33 kV heat shrink joints and terminations in August 2012, ERDA reported on a busbar sleeve, and MSEDCL approved supply to 11 kV in 2015 and 11–33 kV in 2016. AEO status is customs. None belongs in a clause specifying a length of tube.

What each named reference governs

MIL-I-23053/5, Class 2 and Class 3
The United States defence specification for heat-shrinkable electrical insulation sleeving; /5 is the crosslinked polyolefin slash sheet. Two sheets in this range declare it — GSC and Finotube — and both name Class 2 and Class 3 together, as a pair. Neither says what separates the classes, and no qualification reference sits beside the declaration. The GLC sheet, on the same geometry, does not carry it at all.
UL 224, and what VW-1 is
UL 224 is the standard for extruded insulating tubing. VW-1 is its vertical flame rating, run on finished tube rather than on the compound. The rating belongs to a listing, and a file number is the only thing tying one reel to one. GSC prints 125 °C VW-1 against File E328193. Finotube prints the same rating against File E328538.
IEC 60684-3-247
IEC 60684-3 holds the individual specifications in the flexible insulating sleeving series, one sheet per type. Sheet 247 is the one the medium and heavy wall, red insulation and CATV tubes are declared against. The declaration is a single bullet with no report number. Not one property row on those sheets cites it: every value is referred to an ASTM method, to ESI 09-11 or to IEC 216.
ANSI C119.1
Both cold shrink sheets claim the water seal requirements of ANSI C119.1, not the standard entire. That is a clause-level sealing claim with no clause named. Worked through on the cold shrink tubing page.
CSA C22.2
Printed on the GSC sheet with nothing after it, and absent from the Finotube sheet that carries the same MIL and UL lines. C22.2 is a series of Canadian standards, not one document, so the line names a family and stops. For a Canadian job, ask which standard in the series, which certification body and which certificate number.
MIL-I-7444 and ASTM G-21
Two fungus tests, and they do not convert. The thin wall and dual wall sheets rate fungus resistance inert to MIL-I-7444. Both cold shrink sheets report 28 days of exposure with no growth to ASTM G-21. A specification naming one is not met by a sheet carrying the other.
IEC 216, and the heat shock row
IEC 216 carries every temperature band on the heat shrink side. -55 °C to +125 °C on GSC, -40 °C to +110 °C on GMW and GHW, -40 °C to +100 °C on the GDLT double layer tube. The cold shrink band of -40 °C to 105 °C is printed with no method beside it, so the two do not compare as they stand. Heat shock is the row to watch. Thin wall: 250 °C for four hours, no method. Medium and heavy wall, GDLT and the 5:1 tube: 250 °C for 30 minutes to ESI 09-11. Red insulation tube: the same 30-minute row, referred to ASTM D2671. Same condition, same acceptance wording, three different backings.

Dielectric strength: one property, two methods, split by wall class

SheetPrinted valueMethod
GSC thin wall>20 kV/mmASTM D2671
GSC 3X thin wall, 3:1>15 kV/mmASTM D2671
GLC thin wall>15 kV/mmASTM D2671
GDW dual wall>15 kV/mmASTM D2671
Vented thin wall>15 kV/mmASTM D2671
GMW / GHW medium and heavy wall12 kV/mm min., 2 mm wallASTM D149
GMW 5x, 5:112 kV/mm min., 2 mm wallASTM D149
GMWR / GHWR co-extruded12 kV/mm min.ASTM D149
GDLT double layer, inner layer20 kV/mm min.ASTM D149
GRT red insulation22 kV/mm min.ASTM D149
GCTE cold shrink, EPDM14.3 kV/mmASTM D149
GCTS cold shrink, silicone18.0 kV/mm min.ASTM D149

Values as printed on the manufacturer's own sheets. The thin wall family is referred to ASTM D2671 throughout and states no specimen thickness. Everything from medium wall upward, and both cold shrink compounds, go to ASTM D149. Only the GMW/GHW and 5:1 sheets name the specimen — 2 mm. Sources: thin wall and cold shrink.

The same property, two families, two methods

ASTM D149, D257 and D2240 appear in both columns. Everything else differs, so a heat shrink sheet and a cold shrink sheet cannot be read side by side row for row.

PropertyHeat shrink tubeCold shrink tube
Tensile strengthASTM D638. GSC 9 N/mm² min. on one issue and 16 on two others, GMW and GHW 12 N/mm² min. as suppliedASTM D-412. GCTE 9.6 MPa ultimate, GCTS 6.0 MPa min.
ElongationASTM D638. 300% min. on GSC, 350% min. on GMW and GHWASTM D-412. GCTE 750%, GCTS 400% min.
Tear strengthNo tear row on any heat shrink tube sheet in this rangeASTM D-624C 26.3 kN/m on GCTE, ASTM D-624 25.0 kN/m min. on GCTS
HardnessASTM D2240. 45 ± 10 Shore D on GMW and GHWASTM D2240. 40 ± 10 Shore A on GCTS, no hardness row on GCTE
WaterASTM D570 water absorption. 0.15% max. on GSC, 0.5% max. on GMW and GHWManufacturer's internal method. GCTE 1.8% weight gain, 7 days at 90 °C
FungusMIL-I-7444. InertASTM G-21. 28 days exposure, no growth
FlammabilityUL 224 VW-1 pass on GSC, ASTM D2671 pass on GDW, no row at all on GLCNo flammability row on either cold shrink sheet
SealingNo sealing standard. IP68 is claimed where hot melt adhesive is fittedANSI C119.1, water seal requirements only
TemperatureIEC 216. -55 °C to +125 °C on GSC, -40 °C to +110 °C on GMW and GHW-40 °C to 105 °C, no method printed

Which claim carries which backing

ClaimWhere it is publishedWhat backs it
Electrical insulation up to 3.3 kV, GSC thin wallGeneral product properties, thin wall sheetThe sheet alone. No report number, and a third issue of the same sheet rates the series at 600 volts
36 kV, GHW heavy wallOpening paragraph, medium and heavy wall sheetThe duty wording — mechanical protection and outer sealing of a joint of that class, not insulation to it
VW-1 at 125 °C, GSCFlammability row and the specifications blockA UL file number, E328193. The manufacturer's certifications page lists the heat shrink tubes under E328538 instead; the sheet-to-sheet split is on the thin wall page
Conforms to IEC 60684-3-247One bullet each on the medium and heavy wall, red insulation and CATV sheetsNothing beside it. No clause list, no report number, and no property row on those pages cites it
IEC, ASTM, Ul224 and MIL-SPECSpecifications block, both dual wall sheetsFour families and not one document number. The flammability row on the same sheet is referred to ASTM D2671, not to UL 224
Water seal to ANSI C119.1Features list, both cold shrink sheetsA claim scoped to the water seal requirements. No clause and no report
IP68 with hot melt adhesiveOptional adhesive bullet, medium and heavy wall and 5:1 sheetsAn ingress class, not a test result. No immersion depth and no hold time stated
Technical Qualification Report QR 1013Foot of the medium and heavy wall sheet and of the 5:1 sheetThe manufacturer's own report, by number — and the same number on two different products. Ask for the document; a number is a reference
ISO 9001:2015, CPRI, ERDA, MSEDCL, AEOThe manufacturer's certifications pageCompany level. None is a property of a tube and none should be quoted as one

Every claim below is one this site repeats from the manufacturer's published sheets. The third column is what stands behind it, including where that is nothing.

One value, two row labels, and a method that is not the one used elsewhere

ASTM D2671 is the test-methods document for heat-shrinkable tubing — a battery of procedures, not one breakdown test — and the whole thin wall family refers dielectric strength to it. The manufacturer's Finotube web page then repeats the >20 kV/mm figure on a row labelled volume resistivity. Beneath it sits a second volume resistivity row, 1 × 10¹⁴ ohm.cm to ASTM D257. Two rows, one label, and the upper one carries a kV/mm figure. Establish which procedure produced >20 kV/mm before setting it against a D149 result.

Not published — six product pages in this range carry no property table and no standards line

The anti-tracking tube, the non-tracking GAT tube, the GVOT integrated stress control tube, the GLC3 commercial grade tube, the combined thin wall page and the fibre splice protection sleeve publish neither. For some of them a datasheet fills the gap. For GVOT it does not: its sheet carries a six-row selection chart from GVOT 30/12 to GVOT 85/32 and nothing under it. Where a job needs a declared method, ask for the qualification report by number before the part reaches a schedule.

Questions this page gets asked

Which reference should a utility specification name for a heavy wall joint tube?
IEC 60684-3-247. It is the type specification the GMW and GHW range is declared against, and the only reference on that sheet fixing dimensions and required properties together. Then ask for the two things the sheet omits: the report behind the conformance bullet, and confirmation that the issue you hold is current.
Is a tube declared to MIL-I-23053/5 the same as a qualified MIL-spec tube?
No. Declared conformance is the manufacturer's own statement on its sheet. A defence clause requiring qualification asks for evidence against the slash sheet, and no such reference is printed beside the declaration on either the GSC or the Finotube sheet. Close that in writing before an order, not after.
Does a VW-1 rating settle the flammability requirement for my panel?
Only where the panel standard asks for VW-1 by name. VW-1 is a rating on a specimen of tubing; a panel or rolling stock standard sets its own requirement with its own test. Inside this range the flammability row also separates three grades that look alike: GSC is referred to UL 224 VW-1, GDW to ASTM D2671, and GLC has no flammability row at all.
Does the CPRI certificate cover the tube?
Not on its own. It covers 33 kV heat shrink joints and terminations, certified August 2012, and it is written against an assembled kit. The MSEDCL approvals behave the same way — 11 kV in 2015, 11–33 kV in 2016 — they permit supply to a utility and are not test results for a component.
Two issues of the same sheet give different numbers. Which one applies?
The one you can name — and on the thin wall sheets you cannot, because none of the three carries an issue line. Elsewhere in the range they do. Issue 2 July 2024 and Issue 2 February 2025 on the medium and heavy wall sheets. Issue 2 December 2025 on GSC 3X. Issue 1 March 2025 on the EPDM cold shrink sheet, Issue August 2025 on the silicone. Quote the issue where one exists, and get the figure confirmed in writing where it does not.

Ask for the sheet by issue, not by product name

Send the size, the substrate and the standard your specification names. A reply quoting an issue number and a report number is worth more than one quoting a code.