Recovered ID Enquire

Part index · four datasheets out of 175

Cold shrink: stored elastic energy, and the 1.1 kV ceiling

1.1 kV, 8 to 94 mm across seven diameters, −40 °C to 105 °C, and no heat at any point in the job.

The ceiling first, because it settles most enquiries

1.1 kV is where this range stops. Seven diameters cover an 8 to 94 mm application range on copper and aluminium conductor to 1000 sq mm. Ask for cold shrink at 11 kV and there is nothing here to quote against.

Nothing in the range joints or splices anything. Cold shrink appears on four of the manufacturer's 175 published datasheets: tube in EPDM, tube in silicone, a close-ended cap, and a two- or four-core crutch sleeve. Four sealing parts, no joint body, no termination, at any voltage. A specification naming one is naming a different supplier.

This index carries the tube. Codes and diameters are at cold shrink tubing and the size chart. The GCCE cap closes a cut end rather than covering a connection, and anodecap.com holds that subject; cablebreakoutboots.com holds the GCEB crutch sleeve. Both are sister references from this site's publisher, on the same manufacturer's range.

One chart, two prefixes

The EPDM sheet of March 2025 reads GCTE. The silicone sheet of August 2025 reads GCTS — and the manufacturer's own silicone web page reproduces that same chart back under GCTE. Dimensions agree row for row, so the disagreement is in the prefix alone. Put the compound in words beside the code and the ambiguity stops at the order.

The sequence below is a reading, not an installation instruction

Each cold shrink sheet describes recovery in one sentence and prints no numbered procedure. What follows reads that sentence and the sheets' own drawings. Where a leaflet comes in the packet, the leaflet governs.

Where the energy is stored, and when it is let out

  1. Expansion happened once, in a factory

    GCTE 104/42 is supplied at 104 mm minimum and free-recovers to 42 mm maximum. That pair is not a shrink ratio: no cold shrink sheet prints one anywhere, which catches everyone arriving from shrink ratio explained.

  2. A PP coil holds it open, and nothing else does

    All four drawings label the removable core a PP coil. That coil is the only thing resisting the rubber, so storage, transport and handling all happen with the elastomer already under load.

  3. Position it fully before you pull

    Slide the sleeve over the inline connection or the terminal lug and settle it. Lf, the length after free recovery, is 500 mm minimum on all seven codes. The covered length is therefore fixed, and the only decision left is where it starts.

  4. Withdraw the core

    Recovery is immediate. No flame, no gun, no cylinder, no power at the position. No sheet describes re-expanding a recovered part, so treat the pull as one-way and order the spare with the part.

  5. Contact pressure is the whole seal

    Both tube sheets state that no mastic and no tape are required, which leaves stretched rubber bearing on the substrate as the entire water barrier. The sheets put one claim behind that: the water seal requirement of ANSI C119.1.

The window is −40 °C to 105 °C, and only the top of it bites

All four sheets print the same operating range, −40 °C to 105 °C. The bottom end is not the discriminator: the medium and heavy wall polyolefin sheet also starts at −40 °C, and backs it with a low-temperature flexibility test, four hours at −40 °C, no cracking. The top end is where the two technologies part.

105 °C sits 5 °C under the +110 °C continuous limit printed for GMW and GHW, and 20 °C under the +125 °C on the vented thin wall sheet. It also sits 20 °C under 125 °C, the shrink temperature the medium and heavy wall sheet gives — the number a gun would be set by at an adjacent position on the same cable.

Against the cable rather than the tube, 105 °C leaves 15 °C over the 90 °C conductor temperature that XLPE cable to IEC 60502-1 is rated for in normal operation. That headroom is all the sheets support, because none of the four prints a thermal ageing result. The polyolefin sheet prints two: 150 °C for 168 hours, and heat shock at 250 °C for 30 minutes. Ask for an ageing figure before a cold shrink sleeve goes anywhere warm and permanent.

The published envelope, against the heat shrink grades it would displace

Ratings only. What the two mechanisms physically do — crosslinks against stored strain — is set out at heat shrink or cold shrink.

AxisCold shrink — GCTE and GCTSHeat shrink polyolefin
Voltage the chart covers1.1 kV, conductor to 1000 sq mmGMW to 3.3 kV, GHW to 36 kV, both conforming to IEC 60684-3-247
Continuous temperature−40 °C to 105 °C, identically on all four sheets−40 °C to +110 °C on GMW and GHW; −40 °C to +125 °C on the vented thin wall
Dielectric strength14.3 kV/mm in EPDM; 18.0 kV/mm minimum in silicone12 kV/mm minimum at a 2 mm wall on GMW and GHW; over 15 kV/mm on the vented thin wall
Recovered wallNot on either tube chart; the GCCE cap chart prints Tf 3.3 to 3.4 mm1.5 to 3.5 mm across GMW, 2.4 to 4.5 mm across GHW
What you size againstThe application range column; free recovery is published but is not the selection bandRecovered ID and recovered wall
Thermal ageingNo result on any of the four sheets150 °C for 168 hours, plus heat shock at 250 °C for 30 minutes

What the cold shrink range contains

PartCode rangeSizesApplication rangeCompound as published
Tube, EPDMGCTE 20/7 – GCTE 104/4278 – 94EPDM rubber, free of chloride and sulfur
Tube, siliconeGCTS 20/7 – GCTS 104/4278 – 94Silicone, free of chloride and sulfur
End capGCCE-01 – GCCE-05513 – 80EPDM rubber
BreakoutGCEB2-1 – GCEB4-24Ø17–Ø30 to Ø32–Ø50 body; Ø10–Ø14 or Ø12–Ø17 fingersSilicone or rubber on the sheet, EPDM on both web pages
Joint, splice or termination0

Compiled from the four cold shrink datasheets — tube in EPDM, end cap and breakout at Issue 1 of March 2025, silicone tube at August 2025. All dimensions in mm, and the EPDM sheet is the reference for the tube rows. The end cap's feature list claims a 10 to 80 mm size range while its own selection chart starts at 13 mm; the chart figure is used here.

Shelf life is not published, and stored strain is why it matters here

Both tube sheets say the part seals tight and retains resiliency for years. Neither prints a storage period, a maximum time on the coil, a date-code convention, or any recovery figure measured after storage. Polyolefin stock waits at its supplied size; cold shrink stock waits stretched. Ask for a storage limit in writing before committing a part that will sit through a season.

Asked before the size is

Is there a cold shrink joint or splice in this catalogue?
No. Four cold shrink datasheets exist among the manufacturer's 175, and all four are sealing parts. Joints and terminations here are heat shrink, and they begin where cold shrink stops.
What is the highest voltage?
1.1 kV, on copper and aluminium conductor to 1000 sq mm. That describes the cable the sleeve goes onto, not a withstand rating for the sleeve. The 14.3 and 18.0 kV/mm figures are material properties measured on a test piece and do not extend it.
EPDM or silicone?
Never a sizing question — the two charts are identical. Silicone publishes 18.0 kV/mm against EPDM's 14.3, and is the only one of the two carrying a hardness and a volume resistivity. EPDM publishes 750% elongation against 400%, and the only moisture absorption result. Both run −40 °C to 105 °C.
Do I select on the recovered diameter?
No. Use the application range column, which is the band the sleeve will actually grip. Df is a free-recovery figure, the diameter reached with nothing inside, and a GCTE 35/13 landing on a 28 mm joint stops at 28. That is the habit break for anyone arriving from heat shrink, where recovered ID and recovered wall decide.
Does it get me past a refused hot work permit?
Yes, and it is why most readers arrive here: recovery needs no flame, no hot-air gun, no cylinder and no power at the working position. Two limits before a specification is built on it. The range stops at 1.1 kV, and it is tube, cap and crutch only.

Send the diameter and the voltage, in that order

Five lines settle it: outside diameter over the connection at its widest point, conductor size in sq mm, system voltage, whether a hot work permit will be granted there, and whether EPDM or silicone is specified. With those a GCTE or GCTS code can be named — or cold shrink ruled out plainly.